Large Light And Power
AVAILABILITY
This schedule is available in all
territory served by HWL for Lighting And Power Service customers.
TYPE OF SERVICE
Alternating current, sixty-hertz,
120/240 volts nominal, single phase or three phase, or at such higher voltages
as HWL may make available at the point of delivery.
HWL reserves the right of final determination of
voltage and phase of service.
POINT OF DELIVERY
Service to a single contiguous
property will normally be provided at one point of delivery and through one
meter; provided however, that at the option of HWL, service may be provided at
more than one point of delivery on contiguous property in which event, each
point of delivery will be considered a separate account and will be metered and
charged separately.
APPLICABLE TO
Commercial customers having a
connected load greater than 500 KVA but not exceeding 5,000 KVA; or a minimum
billing demand greater than 500 kW but less than 5,000 kW during any month of
the most recent 12 month period.
NET MONTHLY RATE
Customer Charge:
$75.00/Month
Energy
Charge:
May thru September Billing Cycle:
3.38¢
per kilowatt-hour
October thru April Billing Cycle:
2.43¢ per kilowatt-hour
Demand Charge:
Secondary
Service
May thru September
Billing Cycle:
$6.20 per kilowatt of Billing Demand in the month,
but not less
than $3100.00.(1)
October thru
April Billing Cycle:
$5.05 per kilowatt of Billing Demand in the month,
but not less
than $2525.00.(1)
Primary
Service
May thru September
Billing Cycle:
$5.75 per kilowatt of Billing Demand in the month,
but not less
than $2875.00.(1)
October thru April Billing Cycle:
$4.60 per kilowatt of Billing Demand in the month,
but not less
than $2300.00.(1)
(1) Minimum Monthly Billing Demand Charges at 500 kW.
Minimum
monthly billing
demand charge subject to billing
demand clause of this rate schedule.
BILLING DEMAND
The
kilowatts of billing demand for each month will be the average kilowatt load
created by the Customer during the 15 minute period of maximum use during
the month, but not less than 70% of the highest kilowatts of billing demand
established during the 11 (eleven) preceding months or 500KW.
The kilowatts of billing demand will be subject
to the Power Factor Adjustment Clause.
POWER FACTOR ADJUSTMENT
HWL reserves
the right to determine the power factor of the Customer's installation
served hereunder.
Should the
power factor at the time of establishment of any
15 minute period of maximum use during the month be determined to be below
90%, the Customer's Kilowatts of Billing Demand will be adjusted by
multiplying the Kilowatts of Billing Demand by 90% and dividing the result
by the actual power factor at the time of maximum use.
CAPACITY CHARGE FOR HIGHLY
FLUCTUATING LOADS
Should the customer operate equipment with highly fluctuating, intermittent,
or abnormal characteristics that make it necessary for HWL to install any
additional distribution facilities to serve the Customer or to prevent
disturbances to the service of other customers, an additional charge of
$1.00 per month per kilovolt ampere (KVA) or fraction thereof of transformer
capacity installed by HWL to serve the Customer will be added to the
Customer's bill.
PRIMARY DISCOUNT
Upon the request of the Customer,
there will be a discount of 2.2 percent of the kilowatt hour charge on all
monthly bills if electric service is provided at HW&L's primary distribution
voltage of 13.8 KV or higher and the Customer furnishes and maintains all
necessary transformation equipment beyond this point.
FACILITIES CHARGE
HWL shall furnish, install, and
maintain those facilities required to serve the Customer's load with a
monthly charge to the Customer according to the following schedule:
-
A monthly charge of 1.75% will be applied to the total investment in
facilities that are installed,
owned, operated and maintained by HWL.
-
The monthly charge for maintaining facilities installed and owned by HWL
but for
which the customer has paid the full amount to HWL will be 0.57% of the
total
investment in the facilities.
POWER COST ADJUSTMENT
In addition to all other charges,
the amount of the Customer's bill will be increased or decreased by an
amount per kilowatt hour calculated according to the formula in the
Power
Cost Adjustment (PCA) - Rider.
TERMS OF PAYMENT
Customers
who pay within 10 days of the date of the bill will pay the
CURRENT BILL computed on
the Net Monthly Rate.
Bills paid after 10 days from the date of the
bill will include a late payment charge of ten percent (10%) of the first
$30 plus two percent (2%) of the amount over $30.
TERMS AND CONDITIONS
Service will be
furnished under HWL's Standard Terms and Conditions For Electric Service.
|
Type of Service:
|
Electric
|
|
Rate:
|
Rate 4 B (Series 406, 407,
408, 416, 417, 418)
|
|
Class:
|
Large Light & Power
|
|
Adopted:
|
March 21, 2002
|
|
Effective:
|
May 2002
|
|
Cancels:
|
Rate 4, Adopted June 7, 1994
|